IV. Regulation 115. As primary and secondary winding of the transformer can- not occupy the same space, and in addition some insulation — more or less depending on the voltage — must be between them, there is thus a space between primary and secondary through which the primary current can send magnetic flux which does not interlink with the secondary winding, but is a self-induc- tive or leakage flux and in the same manner the secondary current sends self-inductive or leakage flux through the space between primary and secondary winding. These fluxes give rise to the self -inductive or leakage reactances x\ and Xz of the transformer. Or in other words, two paths exist for magnetic flux in the transformer: the path surrounding primary and secondary coils, through which flows the mutual magnetic flux of
... ng, but is a self-induc- tive or leakage flux and in the same manner the secondary current sends self-inductive or leakage flux through the space between primary and secondary winding. These fluxes give rise to the self -inductive or leakage reactances x\ and Xz of the transformer. Or in other words, two paths exist for magnetic flux in the transformer: the path surrounding primary and secondary coils, through which flows the mutual magnetic flux of the transformer, which is the useful ...
... f the transformer can- not occupy the same space, and in addition some insulation — more or less depending on the voltage — must be between them, there is thus a space between primary and secondary through which the primary current can send magnetic flux which does not interlink with the secondary winding, but is a self-induc- tive or leakage flux and in the same manner the secondary current sends self-inductive or leakage flux through the space between primary and secondary winding. Th ...
... inked with one wind- ing only, but not the other one. The latter flux thus does not transmit power, but consumes reactive voltage and thereby pro- duces a voltage drop and a lag of the current behind the voltage, that is, is in general objectionable. The mutual magnetic flux passes through a closed magnetic circuit, with the (vector) difference between primary and second- ary current, that is, the exciting current J0 = /i as m.m.f. The self-inductive flux passes through an open ...
IV. Regulation 115. As primary and secondary winding of the transformer can- not occupy the same space, and in addition some insulation — more or less depending on the voltage — must be between them, there is thus a space between primary and secondary through which the primary current can send magnetic flux which does not interlink with the ...
Concept CandidateHits In SectionStatus
Ether1seeded
Light1seeded
Term CandidateHits In SectionStatus
ether1seeded
Candidate IDOCR / PDF-Text CandidateSource Location
No chapter-local candidates yet--
Candidate IDOCR / PDF-Text CandidateSource Location
theoretical-elements-electrical-engineering-fig-161the coils, it follows that in Fig. 162 the leakage flux interlinked with each turn of each winding, and thus the reactance of the transformer, is materially less than one-quarte…line 18391
Candidate IDCandidate PassageSource Location
No chapter-local candidates yet--
  • Impedance / reactance: Translate historical opposition terms into modern impedance, admittance, conductance, susceptance, and complex-plane notation.
  • Magnetism: Track flux, reluctance, permeability, magnetizing force, and loss language against modern magnetic-circuit terminology.
  • Complex quantities: Track how Steinmetz preserves geometric rotation and quadrature while translating the same operation into symbolic form.
  • Alternating current: Compare Steinmetz’s AC language with modern sinusoidal steady-state analysis, RMS quantities, phase, and phasor notation.
  • Ether references: Verify exact wording before drawing conclusions. Ether language must be separated from later interpretive systems.
  • Magnetism: Centrifugal/divergent magnetic-field readings are interpretive overlays, not automatic historical claims.
  • Ether references: If Steinmetz mentions ether, quote only the verified source words first; any broader ether-field synthesis belongs in a labeled interpretive layer.
  1. Open the full source text and the scan or raw PDF.
  2. Verify the chapter boundary and surrounding context.
  3. Promote exact quotations only after checking the source image.
  4. Move mathematical candidates into canonical equation pages only after formula typography is corrected.
  5. Move diagram candidates into the diagram archive only after image extraction, crop verification, and manifest creation.
  6. Keep Steinmetz wording, modern translation, and ether-field interpretation in separate labeled layers.