CHAPTER XVI LOAD BALANCE OF POLYPHASE SYSTEMS 163. The total flow of power of a balanced symmetrical poly- phase system is constant. That is, the sum of the instantaneous values of power of all the phases is constant throughout the cycle. In the single-phase system, however, or in a polyphase system with unbalanced load, that is, a system in which the different phases are unequally loaded, the total flow of power is pulsating, with double frequency. To balance an unbalanced polyphase system thus requires a storage of energy, hence can not be done by any method of connection or transformation. Thus mechanical momentum acts as energy-storing device in the use as phase bal- ancer, of the induction or the synchronous machine. Electrically, energy is stored by inductance and by capacity. The question then arises, whether by the use of a reactor, or a condenser, con- nected to a suitable phase of the system, an unequally loaded polyphase system can be balanced, so as to give constant power during the cycle. In interlinked polyphase circuits, such as the three-phase sys- tem, with unbalanced load carried over lines of appreciable im- pedance, the voltages of the three phases become unequal. This makes voltage regulation more complicated than in a balanced system. A great unbalancing of the load, such as produced by operating a heavy single-phase load, as a single-phase railway or electric furnace, greatly reduces the power capacity of lines, trans- formers and generators. Unbalanced load on the generators causes a pulsating armature reaction: at single-phase load, the armature reaction pulsates between more than twice the average value, and a small reversed value, between f (cos a + 1) and F(cos a — 1), where cos a is the power-factor of the single-phase load. Especially in alternators of very high armature reaction, as modern steam-turbine alternators, a pulsation of the armatiu^ reaction is very objectionable. It causes a pulsation of the field flux, leading to excessive eddy-current losses and consequent re- duction of the output. The use of a squirrel-cage winding in the 314 LOAD BALANCE OF POLYPHASE SYSTEMS 315 field pole faces of the single-phase alternator reduces the pulsation of the field flux, but also increases the momentary short-circuit stresses. Thus, it is of interest to study the question of balancing unbal- anced polyphase circuits by stationary energy-storing devices, as reactor or condenser. 164. Let a voltage, e = E cos (1) be impressed upon a non-inductive load, giving the current i = I cos (2) The power then is where p = ei = EI cos^ = ^ (1 + cos 2 ) = Q + Q cos 2 « (3) = f (4) that is, in a non-inductive single-phase circuit, the power consists of a constant component, Q--2' and an alternating component, EI = "2- cos 2 0, of twice the frequency of the supply voltage, and a maximum value equal to that of the constant component. The instantane- ous power thus pulsates between zero and 2 Q, by equation (3). If the circuit is inductive, of lag angle a, the current is i = I cos (0 — a) (5) and the instantaneous power thus, p — EI cos 4> cos (0 — a) = -rt" cos a + cos (2 — a) = P -h Q cos (2 - a), thus consists of a constant component, P = -2- cos a = Q cos a (7) 316 ELECTRIC CIRCUITS and an alternating component, Q cos (2 — a) ; it thus pulsates between a small negative and a large positive value, P - Q and P + Q. If the circuit is completely inductive, that is, the current lags IT 90° or 2 behind the voltage, the current is i = / cos (« - I) (8) and the instantaneous power thus, p = EI cos cos(<^ — ^j = -^ sm 2 = Qcos(20-^)i (9) Thus, the power comprises only an alternating component, but no continuous component; in other words, no power is consumed, but the power surges or alternates between +Q and — Q, that is, power is stored and then again returned to the circuit. If the circuit is closed by a capacity, C, the current leads the TT impressed voltage by ^, thus is i = / cos (« + I) (10) and the instantaneous power thus, p = EI cos + l) = -Q cos(2 « - ^) • 166. If a number of voltages, ei = Ei cos (<^ — 7i) (12) * "Engineering Mathematics," Chapter III, paragraphs 66 to 75. LOAD BALANCE OF POLYPHASE SYSTEMS 317 of a polyphase system, produce currents, ii = li cos ( — yi - ai) (13) the instantaneous power of each voltage e* is Pi = edi = Q<{cos ai + cos (2 - 2 7i - ai) ] (14) and the total instantaneous power of the system thus is V = 2)pi = SQ< cos ai + SQi cos (2 <^ — 2 7* — «») = P + Q cos (2 <^ - a) (15) where P = SQiCOStti (16) is the total effective power of the system, and Q = SQi cos (2 - 2 7i - «») (17) is the total resultant alternating component of power, or the resultant power pulsation of the system. Thus, the power of the polyphase system pulsates, with double frequency, between P — Q and P + Q. In this case, P may be greater than Q, and frequently is, and the power thus pulsates between two positive values, while in the single-phase circuit (6) it pulsated between positive and negative value. It thus can be seen, that in any system, polyphase or single- phase, with any kind of load, the total instantaneous power of the system can be expressed, p = P H- Q cos (2 - a) (18) where P is the constant component of power, and Q the amplitude of the double-frequency alternating component of power, and Q may be larger or smaller than P. It must be noted, that Q is not the total reactive power of the system — which would have to be considered, for instance, in power-factor compensation etc. — but Q is the vector resultant of the reactive powers of the individual circuits, while the total reactive power of the system is the algebraic sum of the individual reactive powers (see "Theory and Calculation of Alternating- current Phenomena," Chapter XVI). Thus, for instance, in a system of balanced load, even if the load is reactive, Q = 0. Thus, Q is the unbalanced reactive 318 ELECTRIC CIRCUITS power of the system, and does not include the reactive power, which is balanced between the phases and thereby gives zero as vector resultant. 166. The expression of the power of a polyphase system of gen- eral unbalanced load is by (15) p = P + Q cos (2 <^ - a) (19) this also is the expression of power of the single-phase load of lag angle a, of the impressed voltage and current, e = E cos 1=1 cos (

into the phase e'. The power of (22) (23) then is p' = Q'cos(2<^-2<8-|) (24) where Q' = ^ (26) and the total power of the system, comprising (19) and (25), thus is Po = p + p' = P + Q cos (2 <^ - a) H- Q' cos ^2 <^ - 2 18 - ^) and this would become constant, and the double-frequency term eliminated, that is, the system would be balanced, if Q' and P are chosen so that Q cos (2 - a) + Q' cos (2 « - 2/3 - I) = (26) LOAD BALANCE OF POLYPHASE SYSTEMS 319 hence, & = Q (27) 2 - 2 18 - I = 2 - a - IT or, thus. /3 = f + I (28) 2 ^ ?' = ^ (29) e' = E' cos [0 - (I + I) ] (31) is the voltage, which, impressed upon a reactor of reactance, x = §Q (30) balances the power, P = P + cos .(2 - a) (24) of an unbalanced polyphase system. That is, e' = E' cos [* - (f + J) ] (31) impressed upon the reactance, x, gives the current, '■-^-[*-(i+T)] »^' and thus the power, p'-«eo.[*-(| + |)]cos[*-(J + %')] = - e COS (2 <^ - a) (33) and this reactive power, p', added to the unbalanced polyphase power, p, gives the balanced power, p = p + p' = P. 167. Comparing (31) with (20) or (24), it follows: The unbalanced load of a single-phase voltage, ft e = E cos 0, 320 ELECTRIC CIRCUITS of lag angle, a, or in general, the unbalanced load of a polyphase system with the resultant instantaneous power of lag angle, a, p = P + Q cos (2 « - a) can be balanced by a wattless reactive load, p', having the same volt-amperes, Q', as the alternating component, Q, of the imbal- anced load, and having a phase of voltage lagging by a .T 2 "^4 or by 45° plus half the lag angle, a, of the unbalanced load or un- balanced single-phase current. Just as the unbalanced polyphase load, p, (24) may be single- phase load on one phase, or the vector resultant of the loads on different phases, so the wattless reactive compensating volt- amperes (33) may be due to a single reactor connected into the compensating voltage, e', (31), or may be the vector resultant of several voltages, e'l, loaded by reactances, Xi, so that their vector resultant is p' (33). If a capacity is used for energy storage in balancing unbalanced load (24), the compensating voltage (22), e' = E' cos (<^ - j8), impressed upon the capacity gives the reactive leading current, 2' =rcos(«-i8 + |) (34) hence the compensating reactive power, p' = E'rco8(2-2fi + ^ (35) and therefrom, by the same reasoning as before, ^ = 1+^ (36) e' = 4cos<^-(|+^)] (37) That is, when using a capacity for balancing the load, the com- pensating voltage, e', has the phase, a, 3 TT LOAD BALANCE OF POLYPHASE SYSTEMS 321 or, what is the same as regards to the power expression, a TT 2-4' thus lags by half the phase angle, a, minus 45° (or plus 135°). 168. As instance may be considered a quarter-phase system with one phase loaded. Let d = E cos €2 = E cos (*-5) (38) be the two phase-voltages of the quarter-phase system. Let the first phase, ei, be loaded by a current lagging by phase angle, a, 2*1 = / cos (<^ — a) (39) while the second phase, €2, is not loaded. The power then is V = eiii EI = -^{cos a + cos(2<^ — a)} (40) and is compensated or balanced by a reactance connected to a compensating phase, e' = E' cos {- p) (41) and consuming the reactive current, i' = r cos[ - p + 1) (42) TT T where the — ^ represents inductive reactance, the + « capacity reactance. The compensating reactive power then is p' = e'i' 'T' E'l and this becomes equal to cos(2<^-2/3T0 (43) for 2" c^s (2 * - a), ET = EI ^-2+4 21 (44) 322 ELECTRIC CIRCUITS and the compensating circuit thus is e' = i;'co8(0-|T?) •/ T/ / . a _^ 3 w\ it is, then, hence. for = £7' cos (2 <^ - a HF ^) = -EI cos (2 - a) Po = p + p' EI = -^ cos a, a = 0, or non-inductive load, it is e' = E' cos (« T ^) = ^jcos«±cos(«-^) hsnce, if we choose, hence, E' = E \/2, it is /' = ^' e = Ci ± ej (45) (46) that is, connecting the two phases in series, gives the compensat- ing voltage for non-inductive load. Or: "Non-inductive single-phase load, on one phase of a quarter- phase system, can be balanced by connecting a reactance across both phases in series, of such value as to consume a current equal to the single-phase load current divided by \/2, that is, having the same volt-ampere as the single-phase load." 169. In the general case of inductive load of power-factor, a, the compensating voltage (45) can be written, e' =^ W cos(^ ± tJc^s 4> + sin(^ ± 7) sin <^ = E' cos^l ± ^)cos <^ ± cos^^ + 5)^0^(0 - I) J, LOAD BALANCE OF POLYPHASE SYSTEMS 323 or, choosing, E' = £?, thus, /' = /, it is, by (38), 1 e' = Oi^i ± O262 where Ol = cos (1 ± ?) a2 = COS (1 + 1) (47) and the upper sign applies to the reactor, the lower to the con- denser as compensating circuit. The current then is t' = /cos(*-|T^)- (48) The compensating voltage e' thus can be produced by connect- ing a transformer of ratio Oi into the first phase, ei, a transformer of ratio, aj, into the second phase, 62, and connecting their second- aries in series across a reactor or condenser of suitable reactance. The current, i\ in the compensating circuit consumes a current, oif, in the first phase, Ci, and a current, 021', in the second phase, 62. As the latter phase has no load, the total current in the second phase is t2 = 02t' = / cos(2 T ^J cos \^* - 2 ^ T/ the total current in the first phase is ii® = ii + dii' = /jcos { - a) + cos (I ± ^) cos (* - I HF -/) = / cos(<^ — a) + 0.5 cos (* + I) + 0.5 cos { — a ^ t) = 0.5 /] cos (<^ — a) + cos ((j) hF ^) -'H-^i)-(*-l*Dl' hence has the same value as ^2, but differs from it by k ^^ ^^^ ^^ phase, thus has to its voltage, Ci, the same phase relation as ia 324 ELECTRIC CIRCUITS has to its voltage, d. That is, the system is balanced in load, in phase and in armature reaction. In the unbalanced single-phase load, the power-factor is tti = cos a in the balanced load, the power-factor is ax = cos (I + ^) thus, is materially reduced for a reactor as compensator, +-', it is in general increased for a condenser as compensator, —z- 170. Instead of varying the phase angle of the compensating voltage, e', with varying phase angle, a, of the single-phase load, compensation can be produced by compensating voltages of constant-phase angle, utilizing two such voltages and varying the proportions of their reactive currents, with changes of a. Thus, if ii = / cos (<^ — a), is the load on phase, ei — E cos is not loaded, thus giving the unbalanced power, EI p = -^{ cos a + cos (2 <^ — a) } (49) as compensating voltage may be used, the voltage of both phases connected in series, e = ei + e^ = ^\/2cos(*-^) (50) and the voltage of the second phase, e2 = ^cos(«-|)- (51) Let, then, i' = /' cos(<^ j-)> be the reactive current of the compensating phase, e, and i'2 = 1^2 cos { — tt), LOAD BALANCE OF POLYPHASE SYSTEMS 325 = — /'2 COS the reactive current of the compensating phase, d. The powers of the two compensating circuits then are p = ei _ Ery/2 2 Ery/2 cos (2 — tt) cos 2 (62) and p'2 = e2i'2 EP. cos (^*-3 (53) and the condition of compensation thus is — cos (2 <^ - a) = — cos2 <^ + -^ cos^^2 - 2) ^^^ or, resolved, (/ cos a — P\/2) cos 2 <^ + (/ sin a — P2) sin 2 <^ = 0, and as this must be an identity, the individual coefficients must vanish, that is, / cos a V2 P2 = / sin a = / cos (a -- ^j (55) thus, the compensating voltages and currents, which balance the single-phase load, ei == E cos ii = / cos (<^ — a) (56) are e = ei + 62 = E\/2 cos / cos a i = ^^^cosU and (-0 (57) ei= E cos ( <^ — |j i'i — — /cos (a — ^jcos^ = / sin a cos ^ (58) 326 ELECTRIC CIRCUITS As seen, this means loading the second phase with a reactor giving the same volt-amperes, EI . -^ sm a, e2i'2 = as the unbalanced single-phase load (56), and thereby balancing the reactive component of load, and then balancing the energy component of the load by the compensating voltage ei + ej, as given by (46). If the single-phase load is connected across both phases of the quarter-phase machine in series, € = 61 + 62 = EV2 cos(«T^) t = ;^cos(«4-^-a) (59) in the same manner the conditions of compensation can be de- rived, and give the compensating circuit, e' = E' cos U - I) i' = /'cos(«-|-^) (60) where ET = EI. For non -inductive load, a = 0, this gives e' = Ci, that is, one of the two phases is compensating phase for the re- sultant. 171. As further instance may be considered the balancing of single-phase load on one phase of a three-phase system. Let 61 = E cos 9 62 = E cos( ^) 63 = E cos (0 - -g^j be the three voltages between the three lines and the neutraL (61) LOAD BALANCE OF POLYPHASE SYSTEMS 327 The voltage from line 1 to line 2, then, is Ci* = 61 — 62 = EVs cos ( or 30°. For other angles of lag, either another phase angle of the balancing voltage is necessary, or, if using the same balancing voltage, the balance is incomplete. Let thus: the load 612 = EV3cos(^it> + '^, i = / cos ( 4- ^ - «j , be balanced by reactive load on the second phase, 613 = EV^ cos (* - I) » i' = / cos ( ^J , it is: power of the load. V = eui EI\/3\ balancing power. I cos a -t- cos (2 4- ^ — a) [ ; EIVS cos (^*+i) LOAD BALANCE OF POLYPHASE SYSTEMS 329 thus, total power, Po = p + p' g/Vs 2 ElVl cos a + cos (20 + I"")- COS (2 + I) and cos 3 = sin(|-«) COS a is the ratio of the remaining alternating component of power, to the constant power, and may be called the coefficient of unbalancing.