CHAPTER XXVII. BALANCED AND UNBALANCED POLYPHASE SYSTEMS. 267. If an alternating E.M.F. : e = E V2 sin (3, produces a current : * = 7V2sin (/? — a), where u> is the angle of lag, the power is : p = ei = 2 £Ssin ft sin (ft — S) = £S(cos a — cos (2 £ — a)), and the average value of power : Substituting this, the instantaneous value of power is found as : Hence the power, or the flow of energy, in an ordinary single-phase alternating-current circuit is fluctuating, and varies with twice the frequency of E.M.F. and current, unlike the power of a continuous-current circuit, which is constant : /-** If the angle of lag £ = 0 it is : p = P (1 — cos 2 0) ; hence the flow of power varies between zero and 2 Pt where P is the average flow of energy or the effective power of the circuit. BALANCED POLYPHASE SYSTEMS. 441 If the current lags or leads the E.M.F. by angle £ the power varies between and cos u> that is, becomes negative for a certain part of each half- wave. That is, for a time during each half-wave, energy flows back into the generator, while during the other part of the half-wave the generator sends out energy, and the difference between both is the effective power of the circuit. If £ = 90°, it is : O rt , " p > that is, the effective power : P = 0, and the energy flows to and fro between generator and receiving circuit. Under any circumstances, however, the flow of energy in the single-phase system is fluctuating at least between zero and a maximum value, frequently even reversing. 268. If in a polyphase system *D ez> *s> • • • • = instantaneous values of E.M.F. ; h) *2, t'a, • • • • = instantaneous values of current pro- duced thereby ; the total flow of power in the system is : p = glt\ -f ! -(- E)) = 2 £Scos w = P, or constant. Hence the quarter-phase system is an unsymmetrical bal- anced system. 3.) The symmetrical «-phase system, with equal load and equal phase displacement in all n branches, is a bal- anced system. For, let : e( = E V2 sin ( ft - — "\ = E.M.F. ; V » / / 2 IT A *',- = 7V2 sin O — S — = current V » V the instantaneous flow of power is : l V « 7 \ » EI \ yr cos a -57-035^2 /?-£- — or p = n E I cos w = T7, or constant. 271. An unbalanced polyphase system is the so-called inverted three-phase system,* derived from two branches of a three-phase system by transformation by means of two transformers, whose secondaries are connected in opposite direction with respect to their primaries. Such a system takes an intermediate position between the Edison three- wire system and the three-phase system. It shares with the latter the polyphase feature, and with the Edison three- * Also called "polyphase monocyclic system," since the E.M.F. triangle is similar to that usual in the single-phase monocyclic system. 444 ALTERNATING-CURRENT PHENOMENA. wire system the feature that the potential difference be- tween the outside wires is higher than between middle wire and outside wire. By such a pair of transformers the two primary E.M.Fs. of 120° displacement of phase are transformed into two secondary E.M.Fs. differing from each other by 60°. Thus in the secondary circuit the difference of potential between the outside wires is V3 times the difference of potential between middle wire and outside wire. At equal load on the two branches, the three currents are equal, and differ from each other by 120°, that is, have the same relative proportion as in a three-phase system. If the load on one branch is maintained constant, while the load of the other branch is reduced from equality with that in the first branch down to zero, the current in the middle wire first decreases, reaches a minimum value of 87 per cent of its original value, and then increases again, reaching at no load the same value as at full load. The balance factor of the inverted three-phase system on non-inductive load is .333. 272. In Figs. 185 to 192 are shown the E.M.Fs. as e and currents as i in drawn lines, and the power as / in dotted lines, for : Fig. 185. Single-phase System on Non-inductive Load. Balance Factor, 0. BALANCED POLYPHASE SYSTEMS. 445 Fig. 186. Single-phase System on Inductiue Load of 60° Lag. Balance Factor, - .333. Fig. 187. Quarter-phase System on Non-inductiui Load. Balance Factor, + 1. Fig. 183. Quarter-phase System on Inductiue Lozd of 60° Lag. Balance Factor, + 1. 446 ALTERNATING-CURRENT PHENOMENA. Fig. 189. Three-phase System on Non-induct'we Load. Balance Factor, + 1. Fig. 190. Three-phase System on Inductive Load of 60° Lag. Balance Factor, + 1. Fig. 191. Inverted Three-phase System on Non-inductive Load. Balance Factor, + .333 BALANCED POLYPHASE SYSTEMS. 447 Fig. 174. Inverted Three-phase System on Inductive Load of 60° Lag. Balance Factor, 0. 273. The flow of power in an alternating-current system is a most important and characteristic feature of the system, and by its nature the systems may be classified into : Monocyclic systems, or systems with a balance factor zero or negative. Polycyclic systems, with a positive balance factor. Balance factor — 1 corresponds to a wattless circuit, balance factor zero to a non-inductive single-phase circuit, balance factor + 1 to a balanced polyphase system. 274. In polar coordinates, the flow of power of an alternating-current system is represented by using the in- stantaneous flow of power as radius vector, with the angle ($ corresponding to the time as amplitude, one complete period being represented by one revolution. In this way the power of an alternating-current system is represented by a closed symmetrical curve, having the zero point as quadruple point. In the monocyclic systems the zero point is quadruple nodal point ; in the polycyclic system quadruple isolated point. Thus these curves are sextics. « 448 ALTERNATING-CURRENT PHENOMENA. Since the flow of power in any single-phase branch of the alternating-current system can be represented by a sine wave of double frequency : the total flow of power of the system as derived by the addition of the powers of the branch circuits can be rep- resented in the form : / = />(! + « sin (2 £- a.)) This is a wave of double frequency also, with c as ampli- tude of fluctuation of power. This is the equation of the power characteristics of the system in polar coordinates. 275. To derive the equation in rectangular coordinates we introduce a substitution which revolves the system of coordinates by an angle o>o/2, so as to make the symmetry axes of the power characteristic the coordinate axes. hence, sin (2 ft - S>0) = 2 sin ^ - ^ ) cos (/? - ^ j = substituted, ^M' + ^j. or, expanded : — P2 (x2 + /* + 2 e A:^)2 = 0, the sextic equation of the power characteristic. Introducing : a = (! + «)/'= maximum value of power, b = (1 — c) P'= minimum value of power; BALANCED POLYPHASE SYSTEMS. 449 it is **?> a + b hence, substituted, and expanded : (*»+/)» - \{a (x + j)2 + b (x -X>T> = 0 the equation of the power characteristic, with the main power axes a and b, and the balance factor: b I a. It is thus : Single-phase non-inductive circuit : / = /> (1 + sin 2 <£), b = 0, a = 2P Single-phase circuit, 60° lag : / = P (1 + 2 sin 2 <£), i*.~+" Single-phase circuit, 90° lag :/ = ^ /sin 2 <£, b = — E I, a = + El 2/, &/a= -1. Three-phase non-inductive circuit : p = P, ^ = 1, a = x^+y* — P2 = 0: circle. & / a = + 1. Three-phase circuit, 60° lag : / = P, 6 = 1, a = 1 a? +/- 7>a = 0 : circle. £/«= + !. Quarter-phase non-inductive circuit :p = P,b = ]-) a = x* _|_ y» _ ^2 = o . circlei ^ / ^ = _|_ i. Quarter-phase circuit, 60° lag : p = P, b = 1, tf = 1 450 ALTERNATING-CURRENT PHENOMENA. Inverted three-phase non-inductive circuit : Inverted three-phase circuit 60° lag :/ = f (1 -\- sin 2 <£), b = 0, a = 2 P (y? + /)3 _ />2 (• x _|_ yy = 0< fila = Qf a and <5 are called the main power axes of the alternating- current system, and the ratio b [a is the balance factor of the system. Figs. 193 and 104. Power Characteristic of Single-phase System, at 60° and 0° Lag. 276. As seen, the flow of power of an alternating-cur- rent system is completely characterized by its two main power axes a and b. The power characteristics in polar coordinates, corre- BALANCED POLYPHASE SYSTEM. 451 spending to the Figs. 185, 186, 191, and 192 are shown in Figs. 193, 194, 195, and 196. Figs. 195 and 196. Power Characteristic of Inverted Three-phase System, at 0° and 60° Lag. The balanced quarter-phase and three-phase systems give as polar characteristics concentric circles. 452 ALTERNATING-CURRENT PHENOMENA.