VI. Characteristic Curves of Alternating-current Generator 15. In Fig. 59 are shown, at constant terminal voltage E, the values of nominal generated e.m.f. E0, and thus of field excitation FQ, with the current 7 as abscissas and for the three conditions, 1. Non-inductive load, p = 1, q = 0. 2. Inductive load of 0 = 60 degrees lag, p = 0.5, q = 0.866. 3. Anti-inductive load of — 6 = 60 degrees lead, p = 0.5, q = -0.866. SYNCHRONOUS MACHINES 139 The values r = 0.1, XQ = 5, E = 1000, are assumed. These curves are called the compounding curves of the synchronous generator. In Fig. 60 are shown, at constant nominal generated e.m.f. EQ, that is, at constant field excitation F0, the values of terminal vol- E = 000 £=5, '•*& z EO.F, 500 20 10 00 80 100 120 UO 160 180 200AMP. FIG. 59. — Synchronous generator compounding curves. tage E with the current I as abscissas and for the same resistance and synchronous reactance r = 0.1, XQ = 5, for the three different conditions, 1. Non-inductive load, p = 1, q = 0, EQ = 1127. 2. Inductive load of 60 degrees lag, p = Q.5, q = 0.866, E0 = 1458. 140 ELEMENTS OF ELECTRICAL ENGINEERING 3. Anti-inductive load of 60 degrees lead, p = 0.5, q = -0.866, E0 = 628. The values of EQ (and thus of FQ) are assumed so as to give E = 1000 at I = 100. These curves are called the regulation curves of the alternator, or the field characteristics of the syn- chronous generator. In Fig. 61 are shown the load curves of the machine, with the 40 60 80 100 120 140 160 180 200 220 240 260 280 AMP. FIG. 60. — Synchronous generator regulation curves. current I as abscissas and the watts output as ordinates corre- sponding to the same three conditions as Fig. 60. From the field characteristics of the alternator are derived the open-cir- cuit voltage of 1127 at full non-inductive load excitation, which is 1.127 times full-load voltage; the short-circuit current 225 at full non-inductive load excitation, which is 2.25 times full-load current; and the maximum output, 124 kw., at full non-induct- ive load excitation, which is 1.24 times rated output, at 775 volts and 160 amp. It depends upon the point on the field SYNCHRONOUS MACHINES 141 characteristic at which the alternator works, whether it tends to regulate for, that is, maintains, constant voltage, or constant current, or constant power, approximately. z L 7 \ H 20 40 60 80 100 120 140 160 180 200 220 240 260 280 AMP. FIG. 61. — Synchronous generator load curves.