B. LIGHTING ONLY I II Time Load = Percent. Time X load Losses Time X losses Losses Time X losses 2hr. IK 125 250 4.10 8.20 3.54 7.08 2hr. H 75 150 2.11 4.22 2.55 5.10 20 hr. Mo 5 100 1.00 20.00 2.00 40.00 S = 500 32.42 52.18 Input 532.42 552.18 Per cent, loss 6.11 9 . 45 Per cent, efficiency 93 .89 90 . 55 As seen, while I and II have the same full-load efficiency, 97.1 per cent., I, the low core-loss type, gives a much higher all-day efficiency, the more so the shorter the time of heavy load, that is, is far preferable for general distribution, as "lighting transformer." Inversely, in large power transformers in transmission systems, the high partial load efficiency of the low core-loss type is of less importance, as such transformers are usually not run at partial load, but with a decrease of load on the system, transformers and generators are cut out and the remaining ones kept loaded. Of ALTERNATING-CURRENT TRANSFORMER 285 importance, however, is low i2r loss. Under emergency conditions requiring overloading of some transformer, the increased loss is all in the copper, and the less therefore the i2ry the less is the danger of destruction by overheating in a case of a temporary overload. Thus the low izr loss type of transformer is preferable for large power units.