LECTURE XI. LIGHT INTENSITY AND ILLUMINATION. A. INTENSITY CURVES FOR UNIFORM ILLUMINATION. 102. The distribution of the light flux in space, and thus the illumination, depends on the location of the light sources, and on their distribution curves. The character of the required illumi- nation depends on the purpose for which it is used: a general illumination of low and approximately uniform intensity for street lighting; a general illumination of uniform high intensity in meeting rooms, etc.; a local illumination of fairly high intensity at the reading-table, work bench, etc. ; or combinations thereof, as, in domestic lighting, a general illumination of moderate inten- sity, combined with a local illumination of high intensity. Even the local illumination, however, within the illuminated area usually should be as uniform as possible, and the study of the requirements for producing uniformity of illumination either throughout or over a limited area thus is one of the main prob- lems of illuminating engineering. The total intensity of illumination, i, at any point in space is proportional to the light intensity, 7, of the beam reaching this point, and inversely proportional to the square of the distance I of the point from the effective center of the light source : If the beam of light makes the angle with the vertical direction, the illumination, i, is thus in the direction , the horizontal illumination, that is, the illumination of a horizontal plane (as the surface of a table), is , 7cos< , ih = i cos 0 = 226 LIGHT INTENSITY AND ILLUMINATION. 227 and the vertical illumination, that is, the illumination of a vertical plane (as the sides of a room), is 7 sin 0 iv = i sin <£ = — —!- •, (3) If, then, in Fig. 95, L is a light source at a distance lv above a horizontal plane P, then, for a point A at the horizontal dis- FIG. 95. tance lh from the lamp, L (that is, the distance lh from the point B of the plane P, vertically below the lamp L), we have: , Lv and the distance of the point A from the light is cos hence, the total illumination at point A is . 7 cos2 () . the horizontal illumination is l 7 cos and the vertical illumination is . 7 cos2 sin (4) (5) (6) (7) (8) where 7 is the intensity of the light source in the direc- tion . Inversely, to produce a uniform total illumination, i0, on the 228 RADIATION, LIGHT, AND ILLUMINATION. horizontal plane P, the intensity of the light source must vary with the angle according to the equation (6) : 7" 1 2 (9) or, if we denote by 70 the vertical, or downward, intensity of the light source, A, - V,2; (10) hence, 7 = ^- (11) gives the intensity distribution of the light source required to produce uniform total illumination i0 on a horizontal plane be- neath the light. In the same manner follows from (7) and (8) : To produce uniform horizontal illumination ihQ on a plane P beneath the light source L, the intensity curve of the light source is given by cos3 and, to produce uniform vertical illumination iVQ of objects in the plane P beneath the light source L, 7- /0 (13) cos"

= 90 deg. TABLE I.— (Figs. 95 and 96.) UNIFORM DISTRIBUTION ILLUMINATION CURVES. f. COS (p. Total. 1 Horizontal. 1 Vertical. 1 degrees. cos2 cos3 sin ^ cos2 0 1 1 1 00 5 996 1.01 1.015 11.60 10 985 1.03 1.045 5.90 15 966 .07 1.11 4.30 20 940 .13 1.20 3.30 25 906 .22 1.35 2.88 30 866 .33 1.54 2.66 35 819 .49 1.82 2.59 40 766 .70 2.22 2.64 45 707 2.00 2.83 2.83 50 643 2.43 3.73 3.17 55 574 3.03 5.27 3.70 60 500 4.00 8.00 4.60 65 423 5.59 13.20 6.16 70 342 8.35 24.4 8.90 75 259 15.10 58.3 15.60 80 174 33.00 190.0 32.50 85 087 132.00 152.0 133.00 90 0 00 00 00 103. Therefore, in the problem, as it is usually met, of pro- ducing uniform intensity i0 over a limited area, subtending angle 2 aj beneath the light source, the intensity of the light source 230 RADIATION, LIGHT, AND ILLUMINATION. FIG. 96. FIG. 97, LIGHT INTENSITY AND ILLUMINATION. 231 should follow (11) for 0 < < a>. Beyond <£ = a>, the intensity may rapidly decrease to zero — as would be most economical, if no light is required beyond the area subtended by angle 2 co. This, for instance, is the case with the concentrated lighting of a table, etc. However, the intensity beyond (f> = to may follow a different curve, to satisfy some other requirements, for instance, to produce uniform illumination in a vertical plane. Thus in domestic lighting, for the general uniform illumination of a room by a single illuminant, the intensity curve would follow equation (11) up to the angle a> — if 2 w is the angle subtended by the floor of the room from the light source — and for $ > cu the intensity curve would follow the equation, / = -4-r, (14) sin2 which gives uniform illumination in the vertical plane, that is, of the walls of the room. In Fig. 98 are shown intensity curves of a light source giving uniform illumination in the horizontal plane beneath the lamp, from 0 to CD, and the same uniform illumination in the vertical plane from $ = a> to = 90 deg., as diagrammatically shown in Fig. 97; that is, uniform illumination of the floor of a room and (approximately) its walls, by a lamp located in the center of the ceiling, where cu is the (average) angle between the vertical and the direction from the lamp to the edge of the floor: I for co = 30 deg.; or diameter of floor -f- height of walls = 2 2 tan 30 deg. = —==1.15. II for co = 45 deg.; or diameter of floor -j- height of walls = 2 tan 45 deg. = 2. III for aj = 60 deg.; or diameter of floor -H height of walls = 2 tan 60 deg. = 2 V3 = 3.46. IV for a) = 75 deg.; or diameter of floor -f- height of walls = 2 tan 75 deg. = 7.46. These curves are drawn for the same total flux of light in the lower hemisphere, namely, 250 mean hemispherical candle power; 232 RADIATION, LIGHT, AND ILLUMINATION. or, 1570 lumens. The vertical or downward intensities 70 are in this case: I: aj = 30 deg.; 70 = 428 cp. II: cu = 45 deg.; 70 = 195 cp. Ill: w = 60 deg.; 70 = 95 cp. IV: aj = 75 deg.; 70 = 41.5 cp. The values are recorded in Table II, in column I, for equal downward candle power 70, and in column a, for equal light flux, corresponding to 1 mean hemispherical candle power. TABLE II. — (Figs. 97 to 99.) INTENSITY CURVES. Uniform illumination from vertical = 0 to = « degrees from verti- cal, and (a) Uniform illumination (on vertical plane) from = w to horizontal 0 = 90 deg. (6) No illumination beyond = w. 70 for unity illumination at 0 = 0. a and 6 for mean hemispherical candle power 1, or 2 TT lumens. . ca = 30 deg. w = 45 deg. a> = 60 deg. to = 75 deg. /0< a. 6. V a. b. V a. b. I0- a. 6. 0 5 10 .00 .01 1.03 1.71 1.72 1.76 3.73 3.76 3.83 1.00 1.01 1.03 0.78 0.79 0.80 1.57 1.58 1.62 1.00 1.01 1.03 0.38 0.385 0.39 0.67 0.67 0.685 1.00 1.01 1.03 0.166 0.168 0.172 0.222 0.224 0.229 15 20 25 .07 .13 .17 1.83 1.93 2.00 3.98 4.20 4.35 1.07 1.13 1.22 0.83 0.88 0.95 1.68 1.77 1.99 1.07 1.13 1.22 0.41 0.43 0.465 0.71 0.75 0.81 1.07 1.13 1.22 0.178 0.188 0.203 0.237 0.251 0.271 30 35 40 1.20 1.01 0.81 2.05 1.73 1.38 4.47 3.57 2.24 1.33 1.49 1.70 1.03 1.16 1.32 2.08 2.33 2.66 1.33 1.49 1.70 0.51 0.57 0.65 0.89 0.99 1.13 1.33 1.49 1.70 0.221 0.248 0.283 0.295 0.331 0.377 45 50 55 0.67 0.57 0.50 1.14 0.98 0.85 0.57 0 1.80 1.70 1.49 1.40 1.32 1.16 2.85 2.50 1.10 2.00 2.43 3.03 0.76 0.93 1.16 1.34 1.62 2.02 2.00 2.43 3.03 0.333 0.405 0.504 0.445 0.540 0.672 60 65 70 0.44 0.41 0.38 0.75 0.70 0.65 1.33 1.22 1.13 1.03 0.95 0.88 0.31 0 3.60 3.51 3.39 1.37 1.34 1.29 2.40 2.00 0.80 4.00 5.59 8.35 0.665 0.930 1.39 0.887 1.24 1.86 75 80 85 0.36 0.34 0.34 0.61 0.58 0.58 1.07 1.03 1.01 0.83 0.80 0.79 3.21 3.09 3.03 1.22 1.18 1.16 0.20 0 12.80 12.40 12.10 2.13 2.07 2.02 2.85 2.11 0.67 90 0.33 0.57 1.00 0.78 3.00 1.14 12.00 2.00 0.11 LIGHT INTENSITY AND ILLUMINATION. 233 These curves in Fig. 98 consist of a middle branch, giving uni- form floor illumination, and two side branches, giving uniform side illumination, and are rounded off where the branches join. FIG. 98. Fig. 99 gives the intensity curves for the same angles, w = 30, 45, 60, and 75 deg., for uniform illumination only in the hori- FIG. 99. zontal plane beneath the lamp, but no illumination beyond this; for <£ > a>, the light flux rapidly decreases. The curves in Fig. 99 are also plotted for equal total light flux, of 150 mean hemispherical candle power, or 940 lumens. The 234 RADIATION, LIGHT, AND ILLUMINATION. curve, 0, giving (approximately) uniform illumination within an angle of 20 deg., or for a> = 10 deg., is added to the set; this curve, however, is plotted for one-tenth the light flux of the other curves, 94 lumens, or 15 mean hemispherical candle power. The vertical or downward intensities 70 are in this case, for equal light flux of 940 lumens : I: 'a> = 30 deg.; 70 = 500 cp. II: a) = 45 deg.; 70 = 235 cp. Ill: co = 60 deg.; 70 = 100 cp. IV: aj = 75 deg.; 70 = 25 cp. 0: aj = 10 deg.; 70 = 7000 cp. Fig. 99 best illustrates the misleading nature of the polar dia- gram of light intensities. It is hard to realize from the appearance of Fig. 99 that curves I, II, III and IV represent the same light flux, and curve 0 one-tenth the light flux, that is, little more than half the light flux of a 16-cp. lamp. Curve 0, however, illustrates that enormous light intensities can be produced with very little light flux, if the light flux is concentrated into a sufficiently narrow beam. This explains the enormous light intensities given by search-light beams: for oj = 1 deg., or a concentration of the light flux into an angle of 2 deg. — which is about the angle of divergency of the beam of a good search light —we would get 7 = 700,000 cp. in the beam, with 15 mean hemispherical, or 7.5 mean spherical, candle power light source; and a light source of 9000 mean spherical candle power —a 160-ampere 60- volt arc —would thus, when concen- trated into a search-light beam of 2 deg., have an intensity in the beam of 70 = 210 million candle power, when allowing 75 per cent loss of light flux, that is, assuming that only 25 per cent of the light flux is concentrated in the beam. The numerical values of Fig. 99 are given as b in Table II, for equal light flux corresponding to 1 mean spherical candle power. B. STREET ILLUMINATION BY ARCS. 104. To produce uniform illumination in a plane beneath the illuminant, a certain intensity distribution curve is required, as discussed in A ; for other problems of illumination, correspond- ingly different intensity curves would be needed to give the desired illumination. LIGHT INTENSITY AND ILLUMINATION. 235 It is not feasible to produce economically any desired distribu- tion curve of a given illuminant. Therefore, the problem of illuminating engineering is to determine, from the purpose for which the illumination is used, the required distribution of illu- mination, and herefrom derive the intensity curve of the illumi- nant which would give this illumination. Then from the existing industrial illuminants, or rather from those which are available for the particular purpose, that is selected whose intensity dis- tribution curve approaches nearest to the requirements, and from the actual intensity curve of this illuminant the illumination which it would give is calculated, so as to determine how near it fulfils the requirements. The intensity curve of the illuminant, required to give the desired illumination, depends on the location of the illuminant and the number of illuminants used. Thus if, with a chosen location and number of light sources, no industrial illuminant can be found which approaches the desired intensity curve sufficiently to give a fair approach to the desired illumination, a different location, or different number of light sources would have to be tried. Here, as in all engineering designs which involve a large number of independent variables, judgment based on experience must guide the selection. If so, practically always some industrially available illuminant can be found which sufficiently approaches the intensity curve required by the desired illumination. As example may be discussed the problem of street lighting. This problem is : with a minimum expenditure of light flux- that is, at minimum cost — to produce over the entire street a sufficient illumination. This illumination may be fairly low, and must be low, for economic reasons, where many miles of streets in sparsely settled districts have to be illuminated. This requires as nearly uniform illumination as possible, since the minimum illumination must be sufficient to see by, and any excess above this represents not only a waste of light flux, but, if the excess is great, it reduces the effectiveness of the illumina- tion at the places, where the intensity is lower, by the glare of the spots of high illumination. Uniformity of street illumination thus is of special importance where the illumination must for economic reasons be low; while in the centers of large cities, or in densely populated districts, 236 RADIATION, LIGHT, AND ILLUMINATION. as European cities, the relatively small mileage of streets per thousand inhabitants economically permits the use of far greater light fluxes, and then uniformity, while still desirable, becomes less essential. TABLE III — (Figs 100 and 101.) Intensity: 100 m. sph. cp. Illumination: 200 m. sph. cp.; /„ = 20. a. 6. c. a. 6. c. 1 D. C. D. C. D. C. D. C. «c enclosed enclosed Magnetite Distance. enclosed enclosed Magnetite carbon carbon arc. carbon carbon arc. arc. arc. Clear arc. arc. . Clear Clear inner Opal inner globe. Clear inner Opal inner globe. globe. globe. globe. globe. 4>. 7. 7. 7. x = -• i. i. t. h 0 30 45 59 0 15 22.5 29.5X10~3 10 42 50 63 0.2 22 24.5 30.5 20 92 70 69 0.4 46 33.0 31.0 30 182 107 79 0.6 73 42.5 31.0 40 247 150 102 0.8 73 44.5 30.5 45 270 1.0 67 40.5 29.5 50 257 171 136 1.2 53 35.5 28.0 60 210 181 177 1.4 39 30.5 26.0 70 147 182 226 1.6 30.5 25.5 23.5 75 122 181 243 1.8 24.5 21.5 21.5 80 97 160 250 2.0 19.0 18.0 19.0 85 75 118 249 2.5 11.5 13.0 15.0 90 65 89 197 3.0 7.0 9.5 12.0 100 57 82 47 3.5 5.0 7.0 9.5 110 57 77 16 4.0 3.5 5.5 7.5 120 60 68 5.0 2.0 3.2 4.8 130 35 62 6.0 1.2 2.0 3.4 140 3 56 7.0 1.0 1.4 2.5 150 17 8.0 0.8 1 .0 2.0 9.0 0.5 0.8 1.7 10.0 0.4 0.6 1 1 15.0 0.2 0.3 0.5 20.0 0. 1 0. 1 0.3 25^0 0.1 Q.I 0^2 The arc, as the most economical illuminant, is mostly used for street lighting. Fig. 100 gives the average intensity curves LIGHT INTENSITY AND ILLUMINATION. 237 of three typical arcs for equal light flux of 200 mean spherical candle power: FIG. 100. I. The direct-current enclosed carbon arc, with clear inner globe: a curve of the character discussed in Fig. 82. II. The direct-current enclosed carbon arc, with opal inner globe: a 0:20 III 1,60 1,00 0.4 0,2 08 0,4 06 08 10 12 It 16 18 20 22 24 26 28 FIG. 101. curve of the character discussed in Fig. 92. III. The magnetite arc or luminous arc, with clear globe: a curve of the character discussed in Fig. 89. The numerical values are recorded in Table III, per 100 mean spherical candle power. 238 RADIATION, LIGHT, AND ILLUMINATION. Herefrom then follows, by equations (6) and (4), the (total) intensity, i, in a horizontal plane beneath the lamp, at the horizontal distance lh from the lamp, where lv is the height of the lamp above this plane (the street). These values of illumination, i, are plotted, with x = - as ab- LV scissas, in Fig. 101 and recorded in Table III for lv = 20, and lamps of 200 mean spherical candle power. 105. With lamps placed at equal distances 4o, and equal FIG. 102. heights lv, as shown diagrammatically in Fig. 102, the illumina- tion of any point A of the street surface is due to the light flux of a number of lamps, and not only to the two lamps 1 and 2, between which the point A is situated. As, however, the illumi- nation rapidly decreases with the distance from the lamp, it is sufficient to consider only the four lamps nearest to the point A. The illumination of a point A of the street surface, at a horizon- tal distance lh from a lamp, 1, then is: i = ^ + i2 + ,; + ^ (15) where iv iv is, i4 are the illumination due to the lamps 1, 2, 3, 4, respectively. I j Let -r = P and ^==x; (16) k lv then the directions under which point A receives light are given by: tan fa = x, tan fa = p — x, tan fa = p + x, tan fa = 2 p — x} (17) LIGHT INTENSITY AND ILLUMINATION. 239 and 1 lv2 cos2 / V cos cos /4 cos (18) where Iv I2, 73, I4 are the intensities of the light source in the respective directions v 2, 100 120 110 FIGS. 103, 104. Herefrom are calculated the illumination, i, plotted in Figs. 103 and 104 and recorded in Table IV for lv = 20 ft. ; p = 5, hence lho = 100 ft., Fig. 103, and p = 10, hence lho = 200 ft., Fig. 104, for equal light flux of 200 mean spherical candle power per lamp. As seen, with the same light flux per lamp, the distribution curve III of Fig. 100 gives the highest and the curve I the lowest intensity at the minimum point midways between the lamps, while inversely I gives the highest and III the lowest intensity near the lamp; that is, I, the carbon arc with clear inner globe, gives the least uniform, and III, the luminous arc, the most uni- 240 RADIATION, LIGHT, AND ILLUMINATION. form, illumination, while the carbon arc with opal inner globe, II, stands intermediate. TABLE IV. — (Figs. 101 to 106.) STREET ILLUMINATION. tan 4 = X. Equal light flux per lamp. Equal illumination at minimum. p = 10. p= 5. p = 10. p= 5. a. 6. c. a. &. c. a. b. c. a. 6. c. 0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.5 3.0 3.5 4.0 5.0 15.8 22.8 46.8 74 74 68 54 40 32 26 20 12.7 8.2 6.3 4.9 4.2 23.7 25.7 34.7 44 46 42 37 32 27 23 19.5 14.6 11.3 9 8 6.7 31.7 32.7 33.5 33.5 33 32 30.5 29 26.5 24.5 22 18 15 13 11.5 10.2 20 27 51 78 78 72.5 59 45 37 32 29 25 29 31 40 50 52 48 43 38.5 35 32.5 30 29 41.5 42.5 43 43 43 42.5 41.5 40.5 39 37.5 36 34.5 38 54 111 176 176 162 128 95 76 62 48 30 20 15 12 10 35 38 52 66 69 63 55 48 40 34 29 22 17 13.5 12 10 31 32 32.7 32.7 32.3 31.4 30 28.4 26 24 22 18 15 13 11 10 8 11 20 31 31 29 24 18 15 13 11.6 10 10 11 14 17 18 17 15 13 12 11 10.4 10 12. 1~2 12.3 12.5 12.5 12.5 12.3 12.1 11.8 11.3 11 10.5 10 Ratio of minimum intensities. Ratio of total light fluxes. 1 1.60 2.43 1 1.16 1.38 5.95 2.43 3.75 1.53 2.45 1.00 4.0( 1.3* ) 3.45 2.90 1 1.19 1.00 Ratio of maximum to min. ilium. 17.6 6.9 3.3 3.1 1.8 1.25 The ratio of maximum to minimum illumination is : p = 10 p = 5 I. Carbon arc with clear globe: 17.6 3.1 II. Carbon arc with opal globe: 6.9 1.8 III. Luminous, or magnetite, arc : 3.3 1.25 LIGHT INTENSITY AND ILLUMINATION. 241 As seen, lower values of p, that is, either shorter distances between the lamps, or greater elevation of the lamps above the street surface, give a more uniform illumination, so that, for p = 5, III gives only 25 per cent intensity variation, while, for p = 10, I gives a very unsatisfactory illumination, alternating darkness and blinding glare. •0=2- iO 100 140 160 r\ i FIGS. 105, 106. In Figs. 105 and 106 are plotted, and recorded in Table III, the illuminations for equal minimum intensity midways between the lamps, and for equal distances lho = 200 ft., between the lamps, for p = 5, or lv = 40 ft. height above the street level, Fig. 105. p = 10, or 10 = 20 ft. height above the street level, Fig. 106. To produce this minimum intensity of 0.1 candle feet, with 200 feet distance between the lamps, would require the following mean spherical candle powers : I. Carbon arc with clear globe: 1190 II. Carbon arc with opal globe: 750 III. Magnetite arc: 490 , or 4=40 ft. 800 690 580 242 RADIATION, LIGHT, AND ILLUMINATION. It is interesting to note the great difference in the light flux, required to produce the same minimum illumination, for the three distribution curves. The carbon arc gains in efficiency and in uniformity of illumi- nation by increasing the elevation from 20 to 40 ft., while the magnetite arc loses in efficiency —due to the greater distance from the illuminated surfaces —but makes up for this by the gain in uniformity of illumination. C. ROOM ILLUMINATION BY INCANDESCENT LAMPS. 106. Let Fig. 107 represent the intensity distribution of an incandescent lamp with reflector, suitably designed for approxi- mately uniform illumination in a horizontal plane below the lamp. Such a distribution curve can, for instance, be produced FIG. 107. by a spiral filament F (Fig. 108) located eccentric in a spher- ical globe G, of which the upper part is clear glass and covered by a closely attached mirror reflector R, while the lower part is frosted, as shown diagrammatically in Fig. 105. With this arrangement, half of the light flux issues directly, with approximately uniform intensity in the lower hemisphere, from = 0 to = (f>l} and with gradually decreasing intensity from $ = <£j to 0 at <£ = 2. The other half of the light flux is LIGHT INTENSITY AND ILLUMINATION. 248 reflected from the mirror, and, due to the eccentric location of the filament, the reflected rays are collected into an angle of about 45 deg. from the vertical, and cross each other, thereby producing the intensity maximum at 4> = 30 deg. The intrinsic brilliancy is sufficiently reduced, and the distribution curve smoothed out, by the frosting of the globe as far as not cov- ered by the reflector. The light in the upper hemisphere beyond = (j>2 then is only that reflected by the frosting. The numerical val- ues of intensity of Fig. 107 are recorded in Table V. The mean spherical candle power of the lamp is 12.93, or 163 lumens ; the mean can- dle power in the lower hemisphere is 20.20, or 127 lumens, and the mean candle power in the upper hemi- sphere is 5.66, or 36 lumens. Table V gives the distribution of illumination i in a horizontal plane beneath and above the lamp, for different horizontal distances lh and the vertical distance lv = 1, by equation (6), and the horizontal illumination ih, by equation (7), as discussed in A. These are plotted in Fig. 109, for the lower hemisphere in the lower, for the upper hemisphere in the upper, curve. Assuming now that a room of 24 ft. by 24 ft. and 10 ft. high is to be illuminated by four such lamps, located 6 inches below the ceiling in such a manner as to give as nearly as possible uniform illumination in a plane 2.5 ft. above the floor (the height of table, etc.). FIG. 108. 244 RADIATION, LIGHT, AND ILLUMINATION. TABLE V. — (Figs. 107 to 109.) #. 7. lh lv tan c£. i = I COS2<£ **~ / Ik X = TV i — I cosV fc*- / cos3^ (Upper hemisphere). cos3 tf, if. i'h- 0 10 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 115 120 130 140 150 160 170 180 21.0 22.2 24.5 26.3 25.5 22.5 20.0 19.0 18.0 17.0 16.0 15.0 13.0 11.0 9.5 8.0 7.0 5.5 4.5 3.0 2.5 2.2 2.0 2.0 2.0 0 0.176 0.364 0.577 0.839 1.192 1.732 2.144 2.745 3.732 5.671 11.43 00 11.43 5.671 3.732 2.745 2.144 1.732 1.192 0.839 0.577 0.364 0.176 0 21.0 21.5 21.7 19.8 15.0 9.3 5.0 3.4 2.15 1.13 0.49 0.11 0 0.08 0.29 0.53 0.84 1.00 1.12 1.23 1.47 1.66 1.77 1.94 2.0 21.0 21.3 20.4 17.0 11.5 6.0 2.5 1.44 0.74 0.29 0.08 0.01 0 0.01 0.08 0.14 0.29 0.42 0.56 0.80 1.13 1.43 1.66 1.91 2.0 o 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0 9.0 10.0 21.0 21.25 21.55 21.8 21.6 20.8 19.4 17.7 15.8 13.9 12.2 10.6 9.2 5.1 7.2 6.45 5.8 5.2 4.7 4.2 3.9 2.55 1.8 1.33 1.0 0.8 0.67 0.45 0.33 0.25 0.20 0.17 21.0 21.1 21.3 21.0 20.0 18.5 16.5 14.3 12.3 10.4 8.6 7.2 6.0 5.1 4.2 3.55 3.1 2.65 2.25 1.95 1.7 1.0 0.6 0.37 0.25 0.18 0.13 0.10 0.08 0.05 2.0 2.0 *i'.i 1.5 1.35 1.0 1.2 0.68 Y.08 0.9 0.77 0.63 0.5 0.43 0.38 0.28 0.20 0.17 0.14 0.12 'b'.48 0.35 0.27 0.20 0.13 0.10 0.08 0.06 As the illumination in the space between the lamps is due to several lamps and thus is higher than that at the same horizon- tal distance outside of a lamp, for approximate uniformity of illumination, the distance between the lamps must be con- siderably greater than twice their distance from the side walls LIGHT INTENSITY AND ILLUMINATION. 245 0*6 08 II 246 RADIATION, LIGHT, AND ILLUMINATION. of the room. Locating thus the lamps, as shown diagrammati- cally in Fig. 110, at 5 ft. from the side walls and 14 ft. from each other, the (total) illumination in the lines A, B, C, D in the test plane 2.5 ft. above the floor is calculated. As this plane is 7 ft. beneath the lamps, first the illumination curve in a plane 7 ft. beneath the lamp is derived from that in Fig. 109, by dividing the ordinates by 72 = 49, and multiplying the abscissas by 7. It is given in Fig. 111. FIG. 111. The illumination, i, at any point, P, then is derived by adding the illumination ia, ib, ic, id of the four lamps a, 6, c, d, taken from curve in Fig. Ill for the horizontal distances of point P from the lamps : lhg, lhb, lhc, lhd. These component illuminations are plotted in Figs. 112 to 115; as A , Ab, Ac, Ad in Fig. 112; as Ba, Bb in Fig. 113, etc., and their numerical values, in thousandths of candle feet, recorded in Table VI. In Fig. 116 are shown the four curves of the resultant direct illumination, superim- posed upon each other. 107. To this direct illumination is to be added the diffused illumination G resulting from reflection by ceiling and walls. Let: at = 0.75 = albedo of ceiling; a2 = 0.4 = albedo of walls; (19) while the floor may be assumed as giving no appreciable reflec- tion: a = 0. The diffused light, then, may be approximated as follows: The ceiling receives as direct light the light issuing in the upper hemisphere, or 36 lumens per lamp, thus a total of Lx = 4 X 36 = 144 lumens, (20) LIGHT INTENSITY AND ILLUMINATION. TABLE VI. — (Figs. 110 to 116.) 247 X. Aa. Ab. A. Ba and Bd- B. ca. cb. C. Da- Db and Dc. D. 0 353 71 746 180 690 244 43 600 245 43 600 1 406 74 813 200 738 276 44 645 317 49 691 2 438 76 852 218 782 306 44 681 395 55 785 3 442 78 866 234 822 332 45 714 441 62 845 4 438 80 875 244 852 348 45 737 440 70 866 5 429 80 880 247 870 353 45 746 429 79 880 6 438 80 903 244 882 348 45 754 440 90 919 7 442 78 922 234 880 332 45 750 441 101 949 8 438 76 936 218 866 306 44 737 395 114 939 9 406 74 927 200 850 276 44 723 317 125 896 10 353 71 898 180 838 244 43 710 245 135 859 11 298 67 875 162 830 209 42 696 184 143 835 12 247 63 870 144 825 180 41 690 144 144 825 13 flOO 60 129 156 39 115 143 14 167 57 114 136 37 94 135 15 143 54 102 118 35 79 125 16 121 51 90 103 33 66 114 17 104 48 81 90 31 56 101 18 90 45 72 80 30 49 90 19 80 41 63 72 30 42 79 20 70 38 57 64 30 36 70 21 61 35 52 58 29 33 62 22 55 33 48 52 29 30 55 23 52 31 44 47 28 26 49 24 45 2P 40 43 28 23 43 and also receives some reflected light from the walls. Thus, if ^ = total light flux received by the ceiling, and 3>2 = total light flux received by the walls, the light flux received by the ceiling is ^ = L, + b2a23>2, (21) where b2 is that fraction of the light flux issuing from the walls, which is received by the ceiling. And the light reflected from the ceiling thus is : $/= afr = a, (L, + b2a2$>2). (22) The walls receive as direct light the light issuing from the lamps in the lower hemisphere, between the horizontal, = 90 248 RADIATION, LIGHT, AND ILLUMINATION. deg., and the direction, <£ = a) (Fig. 110), from the lamp to the lower edge of the walls. This angle co varies, and averages 30 deg. for that half of the circumference, PQR (Fig. 110), at which the walls are nearest, and 60 deg. for that half, RSTUP, for which the walls are farthest, from the lamp. Hence the 1.0 0.8 0.6 0.4 0.2 Act Ac 12 10 0.8 B 0.6 0.4 G 0,2 BaScd BbStc 6 *c B B G Bfc&c Bakd X x- — ** -^ -^ -* ^» -•>s X / \ -*- ^^ ^^** >J ^ _ ~~ _ - —. •— , — • - — - -, ~- .. •• — 4 8 12 18 20 2* FIGS. 112, 113. light flux received by the walls as directed light, from each lamp, is - I I sin $ d$ + - T / sin $ d$ = 83 lumens; (23) Zt/30° ^^60° or, a total of L2 = 4 X 83 = 332 lumens. (24) LIGHT INTENSITY AND ILLUMINATION. 249 In addition hereto, the walls receive some of the light flux reflected by the ceiling. The total light received by the walls thus is : $2 = L2 + bpfr, (25) where bl is that fraction of the light flux issuing from the ceiling, which is received by the walls. 1.0 0.8 0.6 C G 0.2 Ca Cb Cd 0 Cc 1.0 Cb 12 16 20 0.8 0.8 D O.i 0.2 Dbbd 0 DC Da FIGS. 114, 115. And the light reflected from the walls thus is : *,' - a^2 = a2 (L2 + 6^*,). (26) It thus remains to calculate the numerical values of bl and by Of the light reflected by the ceiling as secondary generator, /, a part is obstructed by the floor, a part received by the walls. 250 RADIATION, LIGHT, AND ILLUMINATION. The floor is a square plane, of the same size, 24 by 24 ft., as the radiator, that is, the ceiling, and at the distance 10. The light intercepted by the floor can thus approximately be calculated as discussed in Lecture X, II, 1, Fig. 82, for circular radiator and circular shades, by replacing the quadratic shade and radia- tor by circular shades of the same area, r2n = 242, and r = 13.5, at the same distance I = 10, hence of the ratio : - = 0.74. Calculated as discussed in Lecture X, II, 1, the floor receives 55 per cent and the walls 45 per cent of the light reflected by the ceiling. Assuming, approximately, that the walls receive the same percentage of the light reflected from the ceiling, as the ceiling receives of the light reflected from the walls, or &2 - &!, (27) equations (21) and (25) become: ^ = L,+ \a2$>2, (28) 2 = L2+ 6^^; (29) hence, _L2+ 2 1 + (30) and the light reflected from the ceiling is $/ = a^ = «A — — * 2 2; the light reflected from the walls is